synse-modbus-ip-plugin's Introduction

CircleCI FOSSA Status

Synse Modbus-IP Plugin

A plugin for ModBus over TCP/IP for Synse Server.

This plugin is a general-purpose plugin, meaning that there are no device-specific implementations for this plugin. Instead, a set of default handlers are provided. Registering devices with the plugin is then simply a matter of passing in the correct configuration.

Note: By default, a device kind will search for a handler based on the name of the device kind. Here, the device handlers for each device kind should be manually overridden in order to get the functionality required for those devices/outputs. See the supported handlers and example config, below.

Plugin Support

Outputs

Outputs should be referenced by name. A single device can have more than one instance of a single output type. A value of - indicates that there is no value set for that field.

Name Description Unit Precision Scaling Factor
current An output type for current (amp) readings. ampere (A) 3 -
voltage An output type for voltage (volt) readings. volt (V) 3 -
si-to-kwh.power An output type for power readings that converts from SI to kWh. kilowatt hour (kWh) 5 2.77777778e-7
power An output type for power (W) readings. watt (W) 3 -
frequency An output type for frequency (Hz) readings. hertz (Hz) 3 -

Device Handlers

Device Handlers define how registers are read from/written to. Each device should specify the device handler it will use via the override key, e.g. handlerName: foobar. Device Handlers should be referenced by name.

Name Description Read Write Bulk Read
input_register A handler that reads from input registers.

Getting Started

Getting the Plugin

You can get the Modbus-IP plugin either by cloning this repo, setting up the project dependencies, and building the binary or docker image

# Setup the project
$ make setup

# Build the binary
$ make build

# Build the docker image
$ make docker

You can also use a pre-built docker image from DockerHub

$ docker pull vaporio/modbus-ip-plugin

Or a pre-built binary from the latest release.

Running the Plugin

If you are using the plugin binary:

# The name of the plugin binary may differ depending on whether it is built
# locally or a pre-built binary is used.
$ ./plugin

If you are using the docker image:

$ docker run vaporio/modbus-ip-plugin

In either of the above cases, the plugin will run but should ultimately fail because they are missing device configurations. It is up to you to provide the configurations for your deployment.

Since the plugin is a general-use plugin, the device handlers is provides are not specific to any device. The devices that are specified must choose the correct handler (see the table above for supported handlers), and must provide the correct info (e.g. register address, read width, etc). See the section below for an example configuration.

Configuration

Device and plugin configuration are described in detail in the Synse SDK Documentation.

There are two additional plugin-specific config schemes for this plugin: the device data config (the config in the data field of a device instance) and the device output data config (the config for an output type's data field). Examples of these configs are shown in the next sections.

Device Data

The device data is specified in the data field of an instance, e.g.

instances:
  - info: example device
    location: r1b1
    data:
      host: 127.0.0.1
      port: 502
      slaveId: 3
      timeout: 15s
      failOnError: false

The supported fields for this config are:

Field Required Type Description
host yes string The hostname/ip of the device to connect to.
port yes int The port number for the device to connect to.
slaveId yes int The modbus slave id for the device.
timeout no (default: 5s) string The duration to wait for a modbus request to resolve.
failOnError no (default: false) bool Fail the device entire read if a single output read fails.

Device Output Data

The device output data is specified in the data field of a device output config, e.g.

outputs:
  - type: voltage
    info: Leg 1 to neutral RMS voltage
    data:
      address: 500
      width: 2
      type: f32

The supported fields for this config are:

Field Required Type Description
address yes int The register address which holds the output reading.
width yes int The number of registers to read, starting from the address.
type yes string The type fot the data held in the registers.

The type values that are supported in the type field are as follows:

Type(s) Description
u32, uint32 unsigned 32-bit integer
u64, uint64 unsigned 64-bit integer
s32, int32 signed 32-bit integer
s64, int64 signed 64-bit integer
f32, float32 32-bit floating point number
f64, float64 64-bit floating point number

Example Config

This section shows an example configuration for an eGauge 4115 Power Metering device. It exposes readings for voltage and frequency via this config.

# Sample Config
# -------------

# The config scheme version
version: 1.0

# Define the location(s) of the device(s)
locations:
  - name: r1b1
    rack:
      name: rack-1
    board:
      name: board-1

# Define the device kinds, instances, and outputs being used.
devices:
  - name: eg4115.power
    instances:
      - info: eGauge 4115 power meter - facility power monitoring
        location: r1b1
        # Specify the name of the handler we will be using
        handlerName: input_register
        data:
          host: 127.0.0.1
          port: 502
          slaveId: 3
          timeout: 15s
          failOnError: false
        outputs:
          # RMS Voltage
          - type: voltage
            info: Leg 1 to neutral RMS voltage
            data:
              address: 500
              width: 2
              type: f32
          - type: voltage
            info: Leg 2 to neutral RMS voltage
            data:
              address: 502
              width: 2
              type: f32
          - type: voltage
            info: Leg 3 to neutral RMS voltage
            data:
              address: 504
              width: 2
              type: f32

          # Line Frequency
          - type: frequency
            info: L1 line frequency
            data:
              address: 1500
              width: 2
              type: f32
          - type: frequency
            info: L2 line frequency
            data:
              address: 1502
              width: 2
              type: f32
          - type: frequency
            info: L3 line frequency
            data:
              address: 1504
              width: 2
              type: f32

Feedback

Feedback for this plugin, or any component of the Synse ecosystem, is greatly appreciated! If you experience any issues, find the documentation unclear, have requests for features, or just have questions about it, we'd love to know. Feel free to open an issue for any feedback you may have.

Contributing

We welcome contributions to the project. The project maintainers actively manage the issues and pull requests. If you choose to contribute, we ask that you either comment on an existing issue or open a new one.

This plugin, and all other components of the Synse ecosystem, is released under the GPL-3.0 license.

License

FOSSA Status

synse-modbus-ip-plugin's People

Watchers

 avatar

Recommend Projects

  • React photo React

    A declarative, efficient, and flexible JavaScript library for building user interfaces.

  • Vue.js photo Vue.js

    🖖 Vue.js is a progressive, incrementally-adoptable JavaScript framework for building UI on the web.

  • Typescript photo Typescript

    TypeScript is a superset of JavaScript that compiles to clean JavaScript output.

  • TensorFlow photo TensorFlow

    An Open Source Machine Learning Framework for Everyone

  • Django photo Django

    The Web framework for perfectionists with deadlines.

  • D3 photo D3

    Bring data to life with SVG, Canvas and HTML. 📊📈🎉

Recommend Topics

  • javascript

    JavaScript (JS) is a lightweight interpreted programming language with first-class functions.

  • web

    Some thing interesting about web. New door for the world.

  • server

    A server is a program made to process requests and deliver data to clients.

  • Machine learning

    Machine learning is a way of modeling and interpreting data that allows a piece of software to respond intelligently.

  • Game

    Some thing interesting about game, make everyone happy.

Recommend Org

  • Facebook photo Facebook

    We are working to build community through open source technology. NB: members must have two-factor auth.

  • Microsoft photo Microsoft

    Open source projects and samples from Microsoft.

  • Google photo Google

    Google ❤️ Open Source for everyone.

  • D3 photo D3

    Data-Driven Documents codes.