De-lurking for a minute. I have a similar library in C, but I thought I would share my experiences here. There are a combination of factors that can impact performance. These are not in order.
- The type of the network module. If you have a Control Logix with an ENBT, you might want to get a cup of coffee between each request. An EN2T is better and a L80-class CPU with its direct 1Gbps Ethernet is much, much better.
- Older systems/firmware can only use ~500-byte packets. Newer can negotiate up to 4000-byte packets. The latter is much much better.
- Unconnected messaging can only use ~500-byte packets. If you want to use the big packets, you need to use ForwardOpen Extended to set up the connection.
- The *Logix systems support multiple requests per packet. Many other systems (all PCCC-class PLCs, Micro800 series and possibly Omron) do not.
For maximum performance I use connected messages to negotiate large packets where possible and request packing where possible. I easily get an order of magnitude performance increase when stacking all those.
Final note: I have found in my testing that the PLC will drop the connection without warning when using connected messaging at least after about five seconds. Part of that time delay is probably due to how the connection is negotiated on my part but I have not been able to change it. So my library cleanly closes the connection to the PLC (via ForwardClose and then SessionClose) after five seconds and transparently reopens it when the client application tries to do a read.
I cannot stress enough the issue of the PLC closing the connection. All you need is some maintenance tech unplugging something for a couple of seconds and your connection to the PLC will be gone. I had no idea that this was happening but when I finally got all the automatic disconnect/reconnect logic working correctly, my users' reported problems dropped significantly.
I hope some of this is helpful.
from node-ethernet-ip.
Can you post your NodeJS code?
from node-ethernet-ip.
Thanks so much for your reply. Here's my code:
const { Controller, Tag } = require('ethernet-ip')
const plc = new Controller()
for (let i = 0; i < 1000; i++)
{
plc.subscribe(new Tag('HugeIntArray[' + i + ']'))
plc.subscribe(new Tag('HugeFloatArray[' + i + ']'))
}
plc.connect('192.168.1.77', 0)
.then(() => {
plc.scan_rate = 250
plc.scan()
})
.catch(e=>{
console.log("error connecting to plc: ", e)
})
plc.forEach(tag => {
tag.on('Initialized', tag => console.log("Tag Init: ", tag.value))
tag.on('Changed', (tag, oldValue) => { if (tag.name=='HugeFloatArray[0]') {
// Only show changed tag #1
console.log("Tag changed ", tag.value)
}})
})
from node-ethernet-ip.
A few other things:
Is the 1769 local to the NodeJS servers?
I also see the the test processor is a 1769 while the production processor is going through a 1756-ENBT. I believe that the 1769 supports fewer packets per second than the 1756-ENBT. Also, the 1769 CPU is going to be showing the load for everything the processor is doing...there’s only one processor. The 1756-ENBT is only handling comms and nothing else.
from node-ethernet-ip.
I would try adding the tags to a tag group, running one read for the tag group, and time how long the read takes.
from node-ethernet-ip.
I tried the following with a polled tag group. It seems to take about the same time (possibly a couple seconds longer).
Was wondering if the 1756-ENBT had more horespower for multiple connections. That may be part of it. The main concern was the large number of connections, as well as the large number of Conn Error and Timeouts, which seemed to indicate that the library was reconnecting too often.
const { Controller, Tag, TagGroup} = require('ethernet-ip')
const plc = new Controller()
const group = new TagGroup()
for (let i = 0; i < 1000; i++)
{
group.add(new Tag(`HugeIntArray[${i}]`))
group.add(new Tag(`HugeFloatArray[${i}]`))
}
plc.connect('192.168.1.77', 0).then(() => {
doRun()
})
function doRun()
{
console.log("Starting poll...")
plc.readTagGroup(group)
.then(() => {
console.log('Poll complete.')
group.forEach(tag => {
//console.log(tag.value)
})
setTimeout(function() { doRun()}, 1000)
})
}
from node-ethernet-ip.
I don’t think I have anything with that many tags running. I have things with maybe 100 or 150 tags at a 50 to 100 ms update rate for displays. I have some larger structures that run at around 1000ms. I think they total around 5k of data. But they’re read as structures, which is much much faster than individual tags for the same amount of data. If I get some time, I can try and setup a test to see what I get out of individual tags at that quantity.
from node-ethernet-ip.
Thanks. How does the TCP connection setup/teardown work in the library? Does it reconnect on each poll, or is the TCP connection left open for the entire session (unless timeout, of course)?
from node-ethernet-ip.
It opens a connection to the processor once and then sends EIP messages for different read/write operations. The connection to the PLC is left open the entire time. I’ve had connections left open in production for at least several months at a time. Possibly longer; I haven’t really checked beyond that. I’ve been using this in production for 2 years though with lots of installations.
from node-ethernet-ip.
I did just a little testing on this. I was on a LAN with a 5069-L330ER processor. I created an array of 1000 DINT and another array of 1000 REAL. Then I added them to a tag group and timed the tag group read. It was 220ms for all 2000 tags. 115ms if I limited it to the first 500 elements of each array. And 27ms if I only did the first 100 elements of each array.
from node-ethernet-ip.
Ugh. I left out an important part about connection drops. They only happen if you stop traffic to the PLC for some reason. If you have a continuous flow of requests, the connections stay up.
from node-ethernet-ip.
I did just a little testing on this. I was on a LAN with a 5069-L330ER processor. I created an array of 1000 DINT and another array of 1000 REAL. Then I added them to a tag group and timed the tag group read. It was 220ms for all 2000 tags. 115ms if I limited it to the first 500 elements of each array. And 27ms if I only did the first 100 elements of each array.
That's amazing. Apparently the L35E just can't handle that much traffic. I had no idea there would be such a difference between the L35E built-in and a standalone NIC.
Additional info:
Here are some time results with the L35E CPU in RUN vs PROG mode, to see if the PLC CPU is the bottleneck.
(Reading 1000 DINT and 1000 REAL tags in one tag group. PLC is programmed to add random values to all 2000 tags every 100ms)
Tests on i5-7200 PC (2.5GHz), wired Ethernet 100Mbit, PC cpu utilization at 6-10%
RUN mode: 1.62, 1.43, 1.53, 1.46, 1.42 (avg 1.49 sec)
PROG mode: 0.94, 0.92, 0.95, 0.21, 0.90 (avg 0.78 sec)
Tests on Raspberry Pi 3B+ rev 1.3, Wifi 2.4GHz, PI cpu utilization at 2-4%
RUN mode: 3.06, 2.52, 2.41, 2.48, 2.42 (avg 2.58 sec)
PROG mode: 1.91, 1.83, 2.06, 1.85, 2.03 (1.94 sec)
So could it be a combination of PLC CPU, network, and computer?
from node-ethernet-ip.
I’m not sure. How do you have your overhead setup in the controller properties? I think I used to set it up to maximize comms on those older processors.
from node-ethernet-ip.
Here is what I get (I don't have an array of REAL, but I read an array of 1000 DINT twice).
The PC is a Dell XPS 13 (2018 model) under Ubuntu Linux 20.10 and the network is crap:
laptop WiFi -> powerline Ethernet -> ancient 100Mbps switch -> PLC.
The PLC is a Control Logix chassis with multiple Ethernet and CPU modules. In the following I hit an L81 CPU module via two paths, first through the 1Gbps port on the CPU module and then through an ENBT module.
Direct port (1Gbps):
Creation of 2 tags took 90ms.
Read of 2 tags took 51ms.
Read of 2 tags took 39ms.
Read of 2 tags took 32ms.
Read of 2 tags took 33ms.
Read of 2 tags took 40ms.
Read of 2 tags took 34ms.
Read of 2 tags took 37ms.
Read of 2 tags took 37ms.
Read of 2 tags took 42ms.
Read of 2 tags took 34ms.
Read of 2 tags took 33ms.
ENBT:
Creation of 2 tags took 294ms.
Read of 2 tags took 285ms.
Read of 2 tags took 224ms.
Read of 2 tags took 265ms.
Read of 2 tags took 251ms.
Read of 2 tags took 230ms.
Read of 2 tags took 223ms.
Read of 2 tags took 218ms.
Read of 2 tags took 227ms.
Read of 2 tags took 211ms.
Read of 2 tags took 243ms.
You can see how much variation I get (mostly due to the WiFi but the powerline Ethernet is not good either). Again, note that this is hitting the same CPU module for both tests.
I also have an L55 CPU on that same chassis with an equally sized tag:
Creation of 2 tags took 317ms.
Read of 2 tags took 277ms.
Read of 2 tags took 303ms.
Read of 2 tags took 271ms.
Read of 2 tags took 286ms.
Read of 2 tags took 273ms.
Read of 2 tags took 277ms.
Read of 2 tags took 298ms.
Read of 2 tags took 268ms.
Read of 2 tags took 291ms.
Read of 2 tags took 263ms.
Definitely worse, but not by a lot.
The biggest difference is that when I hit the L81 on its built-in port, I can negotiate a 4002-byte packet size.
This is via one of the stress test programs I have for my library. It hammers the PLC by reading a tag (or tags) over and over with no delay in between the reads.
Unfortunately I do not have a CompactLogix for comparison.
from node-ethernet-ip.
Related Issues (20)
- Class1 Implicit message
- AB CompactLogix 5069-L310ERS2/B connection via VPN fails
- Add an option to configure the timeout of "Unconnected Send" messages HOT 1
- Changed Event is missed for previously written tags
- Waht is the max Size of a TagGroup? HOT 2
- Decimal precision is not correct HOT 4
- Question: Can I get tag descriptions? HOT 3
- Can't Read Tag by using attribute ID HOT 1
- Error: TIMEOUT occurred while reading Controller Props. - Micrologix 1100 HOT 5
- tag.generateReadMessageRequest is not a function
- Error connecting to PLC: Error: TIMEOUT occurred while reading Controller Props. HOT 4
- Is this Project Still Maintained? HOT 4
- Possible for multiple scan rates without creating a "new" controller for each one? HOT 5
- Preferred disconnection or unsubscribe method?
- String Tags in Compact Logix / Control Logix HOT 1
- Micro820 PLC , Error: <SCAN_GROUP> TIMEOUT occurred while writing Reading Tag Group HOT 1
- PLC.foreach() doesn't work HOT 1
- Software name HOT 1
- Micro Queue is already full at size of 100 HOT 2
Recommend Projects
-
React
A declarative, efficient, and flexible JavaScript library for building user interfaces.
-
Vue.js
🖖 Vue.js is a progressive, incrementally-adoptable JavaScript framework for building UI on the web.
-
Typescript
TypeScript is a superset of JavaScript that compiles to clean JavaScript output.
-
TensorFlow
An Open Source Machine Learning Framework for Everyone
-
Django
The Web framework for perfectionists with deadlines.
-
Laravel
A PHP framework for web artisans
-
D3
Bring data to life with SVG, Canvas and HTML. 📊📈🎉
-
Recommend Topics
-
javascript
JavaScript (JS) is a lightweight interpreted programming language with first-class functions.
-
web
Some thing interesting about web. New door for the world.
-
server
A server is a program made to process requests and deliver data to clients.
-
Machine learning
Machine learning is a way of modeling and interpreting data that allows a piece of software to respond intelligently.
-
Visualization
Some thing interesting about visualization, use data art
-
Game
Some thing interesting about game, make everyone happy.
Recommend Org
-
Facebook
We are working to build community through open source technology. NB: members must have two-factor auth.
-
Microsoft
Open source projects and samples from Microsoft.
-
Google
Google ❤️ Open Source for everyone.
-
Alibaba
Alibaba Open Source for everyone
-
D3
Data-Driven Documents codes.
-
Tencent
China tencent open source team.
from node-ethernet-ip.